Industrial 8-Ch PWM Input Module, Modbus RTU Protocol, Isolated RS485 Interface, Supports Frequency And Duty Cycle Acquisition, With Various Isolation And Protection Circuits

SKU:33919
Part No.:Modbus RTU PWM Input 8CH
Brand:Waveshare

$29.99
PriceQuantity
1
$29.192
$28.793
$28.634+
Related Products:

Details

Industrial 8-Ch PWM Input Module, Modbus RTU Protocol, Isolated RS485 Interface, Supports Frequency And Duty Cycle Acquisition, With Various Isolation And Protection Circuits
Industrial 8-Ch PWM Input module

Modbus RTU Protocol

RS485 Interface

DC 7~36V Wide Voltage


Frequency And Duty Cycle Acquisition

Multiple Isolation Protection Circuits

Industrial 8-Ch PWM Input Module, front view
Features at a glance

The Modbus RTU PWM Input 8CH is an isolated RS485 to 8-Ch PWM PWM input module, supports PWM pulse frequency and duty cycle detection. Adopts Modbus RTU protocol with built-in protection circuits such as power isolation, magnetical isolation, resettable fuse, and TVS.

  • The inputs use high-speed optocoupler isolation and support high-frequency detection
  • Configurable device address (1~255), multi devices can be cascaded on RS485 bus
  • Onboard voltage regulator, supports 7~36V wide range power supply
  • Onboard unibody power supply isolation, provides stable isolated voltage, needs no extra power supply for the isolated terminal
  • Onboard unibody magnetical isolation, allows signal isolation, high reliability, strong anti-interference
  • Onboard resettable fuse and TVS (Transient Voltage Suppressor), effectively suppresses surge voltage and transient spike voltage in the circuit, provides over-current/over-voltage proof, lightningproof & anti-electrostatic
  • Onboard watchdog, for stable output without crashing
  • Rail-mount case design, support stacking combination, easy to install and safer to use
  • 3x LEDs for indicating the MCU status and signal transceiving status
Specifications
Communication interface RS485
Baud rate 4800, 9600, 19200, 38400, 57600, 115200, 128000, 256000
Default communication format 9600, N, 8, 1
Modbus protocol Standard Modbus RTU protocol
Power supply DC 7~36V
Pulse Input Voltage 3.3V ~ 30V
Frequency Detection Range 400Hz ~ 50kHz
Frequency Resolution 0.01Hz
Frequency Accuracy 5‰
Duty Cycle Detection Range 0 ~ 100%
Duty Cycle Resolution 0.01%
Duty Cycle Accuracy 5‰

Primary function

Supports sending Modbus RTU protocol commands via RS485 to acquire PWM pulse signals

Industrial 8-Ch PWM Input Module, primary function
Industrial Grade Isolated Protection

Onboard power and signal dual isolation for RS485 communication, provides stable isolation voltage, features high reliability and strong anti-interference performance. Built-in TVS (transient voltage suppression tube) can effectively suppress the surge voltage and transient peak voltage in the circuit, lightningproof & ESD protection. Built-in resettable fuse and protection diode to ensure stable current and voltage output, provides over-current and over-voltage proof, improves shock-proof performance, suitable for industrial environments with high requirements.

Industrial 8-Ch PWM Input Module, onboard industrial grade isolated protection
Interface introduction
Industrial 8-Ch PWM Input Module, interface introduction
Wide voltage power supply, isolated RS485 interface

Built-in fuse and anti-reverse protection, With Power and Signal Dual Isolation

Industrial 8-Ch PWM Input Module, built-in fuse and anti-reverse protection,
Rail-Mount Support

Supports 35mm standard guide rail, with rail-mount buckle, easy to install.

Industrial 8-Ch PWM Input Module, rail-Mount support
Supports stacking installation
Industrial 8-Ch PWM Input Module, supports stacking installation

Product show

Industrial 8-Ch PWM Input Module, product show

Dimensions
Industrial 8-Ch PWM Input Module, Dimensions
Resources & Services

Weight: 0.095 kg

Quick Overview

  1. Modbus RTU PWM Input 8CH x1
  2. Power supply terminal adapter x1
  3. Screwdriver x1
Modbus RTU PWM Input 8CH