RS485-HUB-2P is an industrial-grade isolated RS485 hub that can expand one RS485 host port into two RS485 sub ports. It can achieve RS485 network relay, expansion, and isolation functions. It adopts a terminal-type power input and a rail-mounted enclosure design, enabling easy installation and cost efficiency. It is suitable for fields such as data acquisition, IoT gateways, security IoT, and intelligent instrument monitoring.

Specifications

Interface standards Compliant with RS485 standard
Physical interface RS485 screw terminals
Communication rate 300~460800bps baud rate (adaptive)
Supported nodes Each RS485 port supports up to 32 nodes
Communication distance 1200m (9600bps), the higher the communication rate, the shorter the distance
Operating mode RS485 two-wire (A, B), half-duplex transparent transmission
Power Supply DC 5~36V
Operating temperature -45 ~ +85℃
Environment humidity <95%RH
Transmission medium Normal parallel cables/twisted-pair cables

Interfaces

RS485-HUB-2P-details-intro.png

Interfaces Description
+5~36V, GND Power supply terminal input
OUT1A~OUT2A, OUT1B~OUT2B RS485 sub ports 1~2
485A, 485B RS485 host port
P1~P2 RS485 1~8 sub port data reception indicators
RXD 485 host port data reception indicator
TXD 485 host port data transmission indicator
POWER Power indicator

Function Description

RS485-HUB-2P-details-5.png

Extension

When the host RS485 device needs to connect 2 RS485 sub stations via a star connection, connect the host station to the host port of the RS485-HUB-2P, and connect the slaves to the sub ports of the RS485-HUB-2P. This can prevent interference between RS485 and achieve effective isolation.

Isolation

Connect one end of the RS485 to the RS485 host port, and the other end to any RS485 sub port. At this point, the RS485 line is effectively isolated, providing protection against lightning strikes and interference. This effectively protects the other end of the RS485 device from being damaged by high voltage and strong current.

Relay

When RS485 cables exceed 1200 meters or longer distances, signals will attenuate and interference will increase. By using RS485-HUB-2P, the communication distance can be extended.

Hardware Connection Diagram

RS485 Point-to-Point Relay Communication

RS485 1-to-2, point-to-point, half-duplex, relay communication​

RS485-HUB-2P-details-7.png

RS485 Point-to-Multipoint Relay Communication

It supports star-type segmentation connection for RS485 bus, enables flexible networking, and features signal relay and amplification functions

RS485-HUB-2P-details-9.png

RS485 Point-to-Multipoint Relay Communication

It supports the cascading of multiple RS485 devices, solving connectivity issues in large systems with multiple node networking, ensuring stable and reliable signal amplification

RS485-HUB-2P-details-11.png

Dimensions

RS485-HUB-2P-details-size.jpg
RS485-HUB-2P-details-19.png

FAQ

 Answer:

It is a device with one host and eight slaves, purely hardware wired, and must meet three prerequisites:

  • 1. The serial port parameters are consistent;
  • 2. The communication protocol is half-duplex, one question and one answer type, such as the Modbus RTU protocol;
  • 3. The device addresses are different. Seven 485 sub ports can be connected to one 485 device or a 485 bus
  • 4. The scanning cycle time set by the program should not be too short. Adjust the time as long as possible, as the device needs sufficient time
  • 5. Cannot be connected in parallel to the host's 485 port; it must be connected in handshake cascading, as shown in the figure below:

600px-485-hub-8P-6.png

{{{5}}}


 Answer:
  • This device is mainly an extension of the physical layer, which does not involve specific communication protocols, but ensures that the electrical characteristics of the RS485 standard, such as differential signal transmission, multi-point communication, etc., are supported at the hardware level.
  • The device does not contain any functionality to change its role or control communication protocols; it is merely a transparent signal forwarder.

{{{5}}}


 Answer:
  • Powered by 24V, the no-load current is 0.02A, 0.24W

RS485-8U-PWR.png

  • Powered by 12V, the no-load current is 0.03A, 0.36W

{{{5}}}


 Answer:

No, you can connect a 120 Ω balanced resistor externally, as shown in the following figure:
600px-RS485-RS485-RS485.png

{{{5}}}


Support



Technical Support

If you need technical support or have any feedback/review, please click the Submit Now button to submit a ticket, Our support team will check and reply to you within 1 to 2 working days. Please be patient as we make every effort to help you to resolve the issue.
Working Time: 9 AM - 6 PM GMT+8 (Monday to Friday)